kW → Amps
Calculate AC current from real power, voltage, phase, and power factor.
Calculated Current
kW to Amps Formula
The current required for a given real power depends on voltage, phase configuration, and power factor.
Three-Phase
Single-Phase
Example
A balanced 3-phase, 480 V system delivers 10 kW at a power factor of 0.90.
Calculated current: ≈ 13.4 A
Electrical Troubleshooting
Measured current is higher than calculated
Check the actual power factor, voltage, load level, equipment condition, and whether the measured power represents the same operating condition as the calculation.
Power factor changes with load
Motors and other inductive loads can have a power factor that varies with operating load. Use the power factor corresponding to the operating condition being evaluated.
Three-phase currents are not balanced
Check phase voltage balance, connections, conductor condition, equipment loading, and the load itself. This calculator assumes a balanced system.
Common Mistakes
- Forgetting the √3 factor for three-phase systems.
- Using line-to-neutral voltage where line-to-line voltage is required for the three-phase formula.
- Assuming power factor is 1.0 for every load.
- Confusing kW with kVA.
- Treating calculated current as equipment nameplate current.
- Ignoring actual operating conditions when comparing the calculation with measured current.
Related Calculators
Engineering Note
Real power, apparent power, and current are related through power factor. A lower power factor requires more current to deliver the same real power at the same voltage.
This calculator assumes a balanced AC system and is intended for estimation and engineering reference. Verify actual equipment ratings, nameplate information, and applicable electrical requirements for installation and protection work.