RTD & PT100 Troubleshooting
A practical field guide to troubleshooting RTD temperature sensors, including PT100 sensors, wiring, resistance measurements, lead resistance, and common failure modes.
What Is an RTD?
RTD stands for Resistance Temperature Detector. An RTD measures temperature by using the predictable change in electrical resistance that occurs as the sensing element's temperature changes.
RTDs are commonly used in industrial automation, process control, HVAC systems, laboratory equipment, and other applications where accurate temperature measurement is required.
Common RTD types include PT100 and PT1000 sensors.
What Is a PT100?
A PT100 is a platinum RTD with a nominal resistance of 100 Ω at 0 °C.
Its resistance increases as temperature increases.
The actual resistance at a particular temperature is determined by the applicable RTD characteristic and standard, such as IEC 60751.
This means a PT100 should not be treated as a simple resistor with a fixed temperature coefficient when high accuracy is required.
RTD Resistance
A PT100 has approximately the following resistance values near common operating temperatures:
| Temperature | Approximate PT100 Resistance |
|---|---|
| 0 °C | 100.00 Ω |
| 25 °C | 109.73 Ω |
| 50 °C | 119.40 Ω |
| 100 °C | 138.51 Ω |
These values are useful as field reference points. For precise temperature calculations, use the applicable RTD standard and sensor specification.
2-Wire, 3-Wire & 4-Wire RTDs
2-Wire RTD
A 2-wire RTD has two conductors connected directly to the sensing element.
The resistance of the connecting wires is therefore included in the measured resistance.
This can introduce significant measurement error when long cable runs or high accuracy are involved.
3-Wire RTD
Three-wire RTDs are common in industrial control systems. The third wire allows the measuring device to compensate for much of the resistance of the connecting leads.
For the compensation to work correctly, the appropriate wires generally need to have similar resistance.
4-Wire RTD
Four-wire RTDs provide a higher-accuracy measurement by separating the excitation and measurement paths.
This configuration can largely eliminate the effect of lead resistance when used with an appropriate measurement circuit.
How to Measure an RTD
A digital multimeter can be used to make a basic resistance check of an RTD.
- Disconnect the RTD from the measuring circuit when appropriate.
- Set the meter to resistance (Ω).
- Identify the sensor conductors.
- Measure the resistance across the appropriate conductors.
- Compare the measured resistance with the expected value.
For a 3-wire RTD, measure the resistance between the conductors according to the sensor's wiring arrangement. Two of the combinations should typically include the sensing element, while the relationship between the readings can help identify the common lead.
Estimating Temperature from Resistance
Once the RTD resistance has been measured, it can be compared with the expected resistance-temperature relationship.
A PT100 measures approximately 119.4 Ω.
That is consistent with a temperature of approximately 50 °C for a standard PT100 characteristic.
For temperatures above 0 °C, a commonly used approximation is:
where the coefficients and applicable temperature range depend on the RTD standard.
For precision work, use the complete standard equation or the manufacturer's calibration data rather than relying on a simplified approximation.
RTD Temperature Calculator → Calculate RTD temperature from resistance for PT100, PT1000, and other supported sensor configurations.Common RTD Faults
Open Circuit
A broken conductor or failed sensing element can produce an open circuit.
Depending on the controller, transmitter, or PLC input, an open RTD may appear as a very high temperature, a fault condition, or another configured failure indication.
Short Circuit
A shorted sensor or conductors can produce an unusually low resistance and therefore an abnormally low indicated temperature or sensor fault.
Incorrect Resistance
A sensor can develop resistance that does not correspond to its actual temperature because of damage, contamination, incorrect sensor type, or wiring problems.
Intermittent Connection
Loose terminals, damaged conductors, vibration, or moisture can cause an RTD signal to change intermittently.
Lead Resistance
One of the most common sources of RTD measurement error is the resistance of the connecting wires.
With a 2-wire RTD, the resistance of both conductors is added directly to the sensor resistance seen by the measuring instrument.
The measuring device may see approximately:
Three-wire and four-wire configurations are commonly used to reduce the effect of lead resistance.
Checking the Controller Input
If the sensor resistance appears correct but the controller indicates the wrong temperature, investigate the input configuration.
Check:
- RTD type
- PT100 vs PT1000 selection
- 2-wire, 3-wire, or 4-wire configuration
- Temperature units
- Input range
- Sensor fault settings
- Input filtering
- Scaling or offset
Field Troubleshooting Workflow
- Verify the actual process temperature. Use a suitable independent measurement when possible.
- Identify the sensor type. Confirm PT100, PT1000, or another RTD type.
- Identify the wiring configuration. Determine whether the sensor is 2-wire, 3-wire, or 4-wire.
- Inspect the wiring. Check terminals, connectors, cable damage, and signs of moisture or corrosion.
- Measure resistance. Compare the measured resistance with the expected value for the actual sensor temperature.
- Check lead resistance. Particularly for 2-wire installations or long cable runs.
- Check controller configuration. Verify sensor type, wiring configuration, scaling, units, and input settings.
- Check the controller input. If the sensor and wiring are correct, investigate the input hardware or signal conditioning.
Common Fault Examples
Example 1: Temperature Reads Extremely High
An open RTD circuit can cause some controllers to interpret the input as an extreme temperature or sensor fault.
Check the sensor and wiring for an open circuit before replacing the controller.
Example 2: Temperature Reads Extremely Low
Check for a shorted sensor or wiring fault. Also verify that the controller is configured for the correct RTD type.
Example 3: Temperature Is Consistently Too High
If the error is consistent, check sensor type, lead resistance, wiring configuration, scaling, and calibration.
Example 4: Temperature Jumps Around
Inspect terminals and wiring for intermittent connections. Vibration, damaged cable, moisture, and loose terminals can cause intermittent RTD readings.
Example 5: PT100 Measures Correctly but Controller Is Wrong
If the measured resistance agrees with the actual temperature, investigate the controller configuration and input hardware.
RTD Temperature Calculator
Use the ControlsCalc RTD Temperature Calculator to convert RTD resistance into temperature and work with common RTD sensor types.
RTD Temperature Calculator → Convert measured RTD resistance into temperature for common RTD sensor types.